Food processing · CIP
Water recovery doubled
- Fault
- A 40,000-litre process water recovery tank ran negative during peak multi-line CIP cycles: water starvation and pump cavitation risk.
- Diagnosis
- Mass balance: 600 L/min demand against 350 L/min inflow at 2 bar. A secondary inlet leg had been isolated and stripped of its float, capping recovery at 50%.
- Action
- Reinstated the inlet with a matching 2-inch float valve, set 100–150 mm below the primary for staged lead-lag recovery without chatter or water hammer.
- Result
- Recovery capacity 700 L/min: the 250 L/min deficit became a 100 L/min surplus.