FMCG · robotic packer line

Drive fault cleared without changing parts

Verified outcome 35 min · £172,500 avoided
Fault
Carry-over belt down. The drive's HF26 fault was classed by the OEM as an IGBT hardware failure needing component replacement: a projected nine-hour outage.
Diagnosis
Earlier workshop testing showed HF26 is classed more conservatively than the drive's own control logic. Motor wiring and earth bonding were checked to rule out a real downstream fault.
Action
Moved the drive into a like-for-like unit to force a full parameter reread and IGBT reinitialisation, with a Unidrive M200 sourced as contingency. Flagged the legacy drive fleet's nuisance-trip trend.
Result
Line back to full speed in 35 minutes. About £172,500 of downtime cost avoided (projected nine-hour outage less the 35 minutes lost, at £20,500 an hour site operating cost).